Minimum earth conductor size (AS/NZS 3000 Table 5.1)

The minimum protective earthing conductor for a given active conductor size under AS/NZS 3000:2018 Table 5.1, from 1 mm² to 630 mm² copper.

AS/NZS 3000:2018 Table 5.1

Copper, per AS/NZS 3000 Table 5.1.

Minimum protective earth

6mm² copper

AS/NZS 3000:2018 · Table 5.1

For an active of 16 mm². A larger earth is always acceptable.

How this is worked out

  • Straight lookup of AS/NZS 3000:2018 Table 5.1 (minimum copper earthing conductor size) by active conductor size.
  • Copper conductors only. The table gives a minimum: a larger earth is always acceptable, and a design may call for one.
  • Table 5.1 sizes the protective earthing conductor; main earthing conductor and equipotential bonding sizes have their own clauses and are not covered.

Common questions

Why is the earth smaller than the active above 6 mm²?+

The earth only carries fault current for the time it takes the protective device to operate, so it can be smaller than the active once the active exceeds 6 mm². Below that, Table 5.1 keeps earth and active the same size.

Does this cover the earth in a twin & earth cable?+

Compare the earth size printed on the cable sheath (or measured) with the result here. Table 5.1 is the minimum regardless of how the cable was manufactured, so a flat cable whose earth is below the figure for its active is undersized for that circuit.

What if the earth I find is undersized?+

Record it as found. The circuit fails the earthing check and the report should say so with the Table 5.1 minimum beside the measured size.

Related guide

AS/NZS 3000 verification: the tests every installation needs

The mandatory verification tests AS/NZS 3000 requires before a new installation is energised — in order, dead before live — and what goes on the report.